![]() ![]() Logoff server and test from RDP connection.If test was successful, click Yes, save these settings for this program option.Click the Start the program… button to test if the modifications were successful.Check The program requires additional permissions option and click Next.Select the Troubleshoot program option. ![]() Right-click on the view.exe program and select the Troubleshoot compatibility option.One method to resolve the issue is to login on to the server as a user having issues and locate the View.exe program installation folder normally found at: C:\Program Files (x86)\Wonderware\InTouch This may be caused by the user rights related to the login used for the connection, specifically to UAC rights on the View.exe program. Applies to: InTouch 2014 R2, Windows Server 2012 R2.Either publish the application or run InTouch WindowViewer as an Administrator”. When you have InTouch 2014 R2 installed on a Server OS you may receive an error while trying to start the InTouch WindowViewer application from an RDP connection stating “ This Modern Application is not published.